Heat Shrinkable Terminations Suitable for 3 Core XLPE/EPR Insulated Cables for 24 kV
CXO/I-1524-SERIES
![]() |
|
DESCRIPTIONSHeat Shrinkable termination designed for 3 Core XLPE/EPR insulated cables for 24 kV. The design has been focused to provide the basic important functions required for medium voltage power cable accessories including the electric performance, stress relief measure, environmental seal, mechanical fatigues and other related performance parameters laid down in different countries for various service conditions. |
SALIENT FEATURES
|
Meets the requirement of IS:13573 (2011), IEC 60502, IEEE 48, 404, CENELEC HD 629-1 & other applicable international quality
Text Discription | Requirement | GTP value |
A.C Voltage withstand test ( Dry ) | 5 minutes at 4.5 U0 | 86 kV |
A.C Voltage Withstand test ( Wet ) | 1 minutes at 4.5 U0 | 76 kV |
D.C Voltage Withstand test | 15 minutes at 4 U0 | 144 kV |
Partial discharge test | 10 Pc Max. at 1.73 U0 | <5 Pc upto 25 kV |
Impulse Voltage withstand test | 10 impulse each polarity at 75KV | 170 kV |
Thermal Short Circuit ( Screen ) | Two short circuit & no visible deterioration | Even confirm to more straight condition |
Thermal Short Circuit ( Conductor ) | Two short circuit & no visible deterioration | Even confirm to more straight condition |
Dynamic Short Circuit | One short circuit & no visible deterioration | Even confirm to more straight condition |
Humidity Test | 300 hours at 1.25 U0 | Passes |
Salt Fog Test | 100 hours at 1.25 U0 | Passes |
Cable Size (sq. mm)
|
Kit code
|
|
25-50
|
CXO-31
|
Enquire Now
|
70-95
|
CXO-32
|
Enquire Now
|
120-185
|
CXO-33
|
Enquire Now
|
240-400
|
CXO-34
|
Enquire Now
|
Cable Size (sq. mm)
|
Kit code
|
|
25-50
|
CXI-31
|
Enquire Now
|
70-95
|
CXI-32
|
Enquire Now
|
120-185
|
CXI-33
|
Enquire Now
|
240-400
|
CXI-34
|
Enquire Now
|